Enphase IQ Battery 5P and 10C system design: counts, backup and solar limits
An IQ Battery 5P stores 5 kWh and delivers 3.84 kVA; an IQ Battery 10C stores 10 kWh and delivers 7.08 kVA. Enphase sizes both the same way: enough units for the largest single load to be backed up, enough for the energy needed through the outage, and the larger of the two. The two do not mix. The 10C runs on the new IQ Combiner 6C and IQ Meter Collar, not on an IQ System Controller, and does not work with 5P, 3T or 10T batteries; Enphase says 5P compatibility will come later. What limits the solar depends on the microinverters: with IQ8 on a 10C system, up to 270% of the batteries' rated kVA; with IQ6 or IQ7, 150%; either way at most 19.2 kVA. In SCE's Los Angeles County territory, 6,168 new solar systems got a 5P from January 2024 to August 2026, and the 10C, first recorded in 2025, made up 25% of the Enphase battery systems from January to August 2026.
In this guide
5P and 10C side by side#
Swipe to see all columns →
| Design point | IQ Battery 5P | IQ Battery 10C |
|---|---|---|
| Energy and power per unit | 5 kWh, 3.84 kVA | 10 kWh, 7.08 kVA |
| Control equipment | IQ System Controller 3, 3G or 3M | IQ Combiner 6C and IQ Meter Collar; no System Controller |
| Most storage | With oversubscription, 40 kWh per System Controller battery port; 80 kWh with System Controller 3 or 3M | Eight units: 30.72 kW, 80 kWh |
| IQ8 solar | Limited by the 64 A PV port (System Controller 3G), or PV + DER ports (3 or 3M) | Up to 270% of battery kVA, at most 19.2 kVA |
| IQ6 or IQ7 solar | Up to 5.76 kVA per battery (150%), or PV shedding | Up to 150% of battery kVA: 10.62 kVA with one battery, at most 19.2 kVA |
| M215 or M250 solar | Up to 150% of battery output, as for IQ6/IQ7; not with System Controller 3M or the IQ Meter Collar | Not compatible with IQ Combiner 6C; legacy Enphase solar on its own gateway counts as third-party solar |
| Third-party or legacy solar | Grid-tied only | Up to 100% of battery kVA, at most 15.36 kVA; shed during outages for now |
| Backup | Whole home or partial home | Whole home, with optional load control; partial home: guide inconsistent |
From Enphase's planning guides: TEB-00004-8.0 (July 2026) for IQ Battery 5P with IQ System Controller 3, 3G or 3M, and TEB-00282-4.0 (February 2026) for IQ Battery 10C with IQ Combiner 6C. kVA: the batteries' rated continuous output. "PV shedding": disconnecting the excess solar when the home goes off the grid.
How many batteries#
- Largest load first. Enphase's first step is the largest single load to be backed up: enough batteries to start and run it, as NEC 710.15(A) requires for a stand-alone system. - Then the energy. The second step is the kWh the backed-up loads use over the outage the customer wants to cover; the number of units is the larger of the two results. - Limits. With battery oversubscription, one IQ System Controller battery port takes up to 40 kWh of 5P, so an IQ System Controller 3G takes up to 40 kWh and a 3 or 3M up to 80 kWh. A 10C system takes up to 8 batteries, 30.72 kW and 80 kWh, and with battery oversubscription up to 4 10C can share one 80 A breaker on the IQ Combiner 6C. - EV charger. An Enphase IQ EV Charger on the 10C system's EV breaker needs at least 2 10C batteries, because the chargers are rated at 32 A or more.
How much solar#
- IQ8 microinverters. With the 5P, the number of IQ8 microinverters is limited by the 64 A continuous rating of the PV port on an IQ System Controller 3G, and of the PV and DER ports together on a 3 or 3M when the DER port carries no battery. With the 10C, IQ8 solar may be up to 270% of the batteries' rated kVA, at most 19.2 kVA on the combiner's PV busbar. - IQ6 and IQ7 microinverters. With the 5P, up to 5.76 kVA of microinverters per battery, 150% of its output; above that, the excess solar must be shed when the home goes off the grid. With the 10C, up to 150% of the batteries' kVA: 10.62 kVA with one battery and at most 19.2 kVA with more. - M Series microinverters. The 5P works with M215 and M250 microinverters under the same 150% limit, but not with an IQ System Controller 3M; Enphase lists M Series as incompatible with the 10C's IQ Combiner 6C. - Third-party or legacy solar. With the 5P, Enphase supports a third-party inverter only in grid-tied systems, without backup. With the 10C, third-party or legacy solar on the combiner's load controller may be up to the batteries' rated kVA, at most 15.36 kVA, and in an outage it is currently shed: it neither runs the home nor charges the batteries.
Backup#
- Whole home or part of it. A 5P system can back up the whole home or a backup panel. A 10C system backs up the whole home, with the IQ Combiner 6C's load controller switching off large loads; for partial home backup the 10C guide is inconsistent: its overview calls it a planned configuration not yet supported, while its section 12 shows supported partial home backup layouts for 200 A and 400 A services; confirm with Enphase. - Full Backup needs backup equipment. In the 10C guide, the Full Backup profile keeps all of the battery for outages and is not available in a grid-tied system, and in every profile the battery charges from the grid up to the reserve so that the backup charge is there when needed.
What was installed#
Swipe to see all columns →
| Enphase battery | 2024 | 2025 | 2026 (Jan–Aug) |
|---|---|---|---|
| IQ Battery 5P | 1,678 | 3,163 | 1,327 |
| IQ Battery 10C | 0 | 98 | 448 |
| IQ Battery 3T or 10T | 831 | 73 | 13 |
| IQ Battery 3 or 10 (first generation) | 342 | 33 | 15 |
New residential solar systems in SCE's service territory in Los Angeles County with an Enphase battery, by year of permission to operate. Additions to existing systems are not included. Source: California DG Stats, Interconnected Project Sites, data through August 31, 2026.
- The 5P is the volume battery. 49% of the 5P systems had a single 5 kWh battery and 37% had two. 92% of them had only IQ8 microinverters; 179 had only IQ6 or IQ7 microinverters, where the 150% limit applies. - The 10C arrived in 2025. 98 systems got one in 2025 and 448 from January to August 2026; 61% had a single battery. - Enphase's share. Enphase batteries went into 20% of the new solar systems with a battery from January to August 2026.
Data limits#
The table summarizes Enphase's planning guides as of the dates above; installation manuals, the local building department and the utility have the final word. The records give the battery model and total kWh as filed, not the controller, the backup configuration or the loads backed up, so they cannot show whether a system was sized for backup. Battery models were read from the generator model text. They cover SCE's territory in Los Angeles County only. This is not engineering advice.
How many Enphase batteries do I need for backup?
Enough to start and run the largest load you want backed up, and enough kWh for the outage you want to cover; Enphase takes the larger of the two. Each 5P adds 5 kWh and 3.84 kVA, each 10C 10 kWh and 7.08 kVA.
Can I mix an IQ Battery 10C with my 5P?
Not yet. Enphase says the 10C and its IQ Combiner 6C do not work with 5P, 3T or 10T batteries or with IQ System Controllers, and that compatibility with the 5P will come in the future.
How much solar can an Enphase battery system have?
With IQ8 microinverters on a 10C system, up to 270% of the batteries' kVA and at most 19.2 kVA; with IQ6 or IQ7, 150%, also at most 19.2 kVA. On a 5P system, IQ8 solar is limited by the System Controller's 64 A PV port, or PV and DER ports together on a System Controller 3 or 3M.
Methodology#
The design rules are from Enphase's technical briefs "Planning the Enphase Energy System" (TEB-00004-8.0, July 2026) and "Enphase Energy System planning with IQ Battery 10C/10CS and IQ Combiner 6C" (TEB-00282-4.0, February 2026, read from a distributor's copy); each sentence and table row used was checked word for word. The records are California DG Stats' Interconnected Project Sites (data through August 31, 2026): SCE, Los Angeles County, residential, new systems with solar and storage, permission to operate from January 1, 2024 to August 31, 2026, with an Enphase battery model among the generators; unit counts are the recorded kWh divided by the unit size. Shares are rounded half up.
Sources#
- Enphase — Planning the Enphase Energy System, technical brief TEB-00004-8.0 (July 2026). https://enphase.com/download/planning-enphase-energy-system-tech-brief
- Enphase — Enphase Energy System planning with IQ Battery 10C/10CS and IQ Combiner 6C, technical brief TEB-00282-4.0 (February 2026). https://www.invertersupply.com/media/data/teb-00282-en-us-ees-iq-bat-10c-10cs-iq-comb-6c.pdf
- California Distributed Generation Statistics — Interconnected Project Sites data set. https://www.californiadgstats.ca.gov/downloads/