120 half-cut cells. Power classes 430–455 W in the CEC list; datasheet covers 440–455 W.
| Model | Pmax | Voc, V | Isc, A | Vmp, V | Imp, A | Efficiency | PTC | CEC listed |
|---|---|---|---|---|---|---|---|---|
| FBM430M7G-BB | 430 W | 41.34 | 13.25 | 34.30 | 12.54 | ≈19.9% | 395 W | Feb 22, 2022 |
| FBM435M7G-BB | 435 W | 41.52 | 13.33 | 34.45 | 12.63 | ≈20.1% | 400 W | Feb 22, 2022 |
| FBM440M7G-BB | 440 W | 41.70 | 13.41 | 34.60 | 12.72 | ≥20.3% | 405 W | Feb 22, 2022 |
| FBM445M7G-BB | 445 W | 41.90 | 13.48 | 34.80 | 12.79 | ≥20.6% | 409 W | Feb 22, 2022 |
| FBM450M7G-BB | 450 W | 42.10 | 13.56 | 35.00 | 12.86 | ≥20.8% | 414 W | Feb 22, 2022 |
| FBM455M7G-BB | 455 W | 42.30 | 13.63 | 35.20 | 12.93 | ≥21.0% | 419 W | Feb 22, 2022 |
| Datasheet | CEC listing test | |
|---|---|---|
| Pmax coefficient γ | −0.33 %/°C | −0.389 %/°C |
| Voc coefficient β | −0.27 %/°C | −0.292 %/°C |
| Isc coefficient α | +0.05 %/°C | +0.044 %/°C |
| Vmp coefficient | ≈ −0.38 %/°C | — |
| Operating cell temperature | — | NOCT 46.6 °C |
| Class | Pmax at NOCT | Vmp × Imp at NOCT | Pmax at 200 W/m² | Low-light efficiency vs STC |
|---|---|---|---|---|
| 430 W | 319.6 W | 31.66 V × 10.09 A | 86.1 W | 100% |
| 435 W | 323.3 W | 31.8 V × 10.17 A | 87.1 W | 100% |
| 440 W | 327 W | 31.93 V × 10.24 A | 88.1 W | 100% |
| 445 W | 330.7 W | 32.12 V × 10.3 A | 89.1 W | 100% |
| 450 W | 334.4 W | 32.3 V × 10.35 A | 90.1 W | 100% |
| 455 W | 338.2 W | 32.49 V × 10.41 A | 91.1 W | 100% |
| Inverter | Max DC input | MPPT | Window source | Panels per string |
|---|---|---|---|---|
| Tesla 1538000-xx-y | 600 V | 60–480 V | datasheet | 3–13 |
| Solis (Ginlong) S6-EH1P10K-H-US | 600 V | 80–520 V | datasheet | 3–13 |
| Solis (Ginlong) Solis-1P7.6K-4G-US | 600 V | 100–500 V | datasheet | 4–13 |
| Qcells Q.VOLT H7.6SX | 498 V | 234–498 V | CEC test window | 9–11 |
| Microinverter | Recommended module power | Max DC input | MPPT | Voc cold / Vmp hot | Check | DC/AC |
|---|---|---|---|---|---|---|
| Enphase IQ8X-80-M-US | 320–540 W | 79.5 V | 43–60 V | 44.5 / 28.4 V | ✗ Not a match: module voltage below MPPT range | 1.17 |
| APsystems (Alt Power System) DS3-L | 265–570 W | 60 V | 28–45 V | 44.5 / 28.4 V | ✓ Within range | 0.57 |
| Enphase IQ8M-72-2-US | 260–460 W | 60 V | 30–45 V | 44.5 / 28.4 V | ⚠ Works; below MPPT at peak heat | 1.37 |
| Enphase IQ8A-72-2-US | 295–500 W | 60 V | 32–45 V | 44.5 / 28.4 V | ⚠ Works; below MPPT at peak heat | 1.28 |
| City | kWh / kW / yr | kWh / panel / yr | kWh / system / yr | Sun, kWh/m²/day |
|---|---|---|---|---|
| Los Angeles | 1,676 | 746 | 11,933 | 6.08 |
| Palmdale | 1,835 | 817 | 13,065 | 6.69 |
| Chula Vista | 1,696 | 755 | 12,076 | 6.11 |
| Huntington Beach | 1,643 | 731 | 11,698 | 5.89 |
| Riverside | 1,696 | 755 | 12,076 | 6.21 |
| Santa Clarita | 1,724 | 767 | 12,275 | 6.28 |
| Panel | Pmax | Efficiency | γ Pmax (CEC) | Voc, V | Isc, A | Size | Warranty | PVEL (product / brand) | SoCal permits (series) |
|---|---|---|---|---|---|---|---|---|---|
| URE (United Renewable Energy) FBM445M7G-BB | 445 W | ≥20.6% | −0.389 | 41.9 | 13.48 | 75.1 × 44.6 in | 25 / 25 yr | — | 3 |
| Qcells Q.TRON BLK M-G2+ 445 | 445 W | ≈22.8% | −0.276 | 40.16 | 13.98 | 67.8 × 44.6 in | 25 / 25 yr | brand 11× (2016–2026) | 40 |
| Silfab Solar SIL-440QD | 440 W | ≈22.6% | −0.294 | 38.97 | 14.25 | 67.8 × 44.6 in | 25 / 30 yr | brand 7× (2017–2025) | 39 |
| Hyundai Energy Solutions HiN-T445NF(BK) | 445 W | ≈22.9% | −0.298 | 39 | 14.46 | — | 25 / 30 yr | brand 5× (2017–2025) | 37 |
The URE (United Renewable Energy) datasheet guarantees at least 20.6% module efficiency for the 445 W class (up to 21% for 455 W). 445 W over 2.16 m² equals about 206 W per square meter.
PVWatts v8 with typical-year weather gives about 746 kWh per year per 445 W panel in Los Angeles and about 817 kWh in Palmdale (20° roof, facing south, 14% system losses).
With γ = −0.33 %/°C, at a 77 °C cell temperature (hottest modeled hour in Palmdale) output is about 17.1% below the STC rating.
With the Tesla 1538000-xx-y (max DC 600 V, MPPT from 60 V, datasheet) in Los Angeles the calculator gives 3–13 panels per string (Voc at 2 °C = 44.5 V, Vmp at 74 °C cell = 28.4 V). Final design must follow the inverter manual and NEC 690.7.
Voltage check against the APsystems (Alt Power System) datasheet: Voc when cold 44.5 V vs max input 60 V; Vmp when hot 28.4 V vs MPPT low 28 V; recommended module power 265–570 W. Confirm on the microinverter maker’s compatibility list.
25 years on the product and 25 years on performance: at least 84.8% after 25 years (manufacturer datasheet).
75.1 × 44.6 × 1.38 in (1,908 × 1,134 × 35 mm), 53.4 lb (24.2 kg).
Building permits name this series 3 times (Jun 2024 – Mar 2025). The most active licensed installers are T & T Construction Services.