Cali-GrafCali-Graf
Solar panelFirst Solar

First Solar FS-6430A-P-x

264 cells. Power classes 400–460 W in the CEC list.

CEC listed · Oct 21, 2021UL 61730
Power class
  • Power (STC)430 WCEC nameplate
  • Efficiency≈17.1%calculated from area
  • %/°C Pmax−0.307CEC listing test
  • PTC / STC92%PTC 396 W (CEC)

Power classes

CEC PV Module List (Oct 7, 2026) · Cali-Graf calculation · 13 models
ModelPmaxVoc, VIsc, AVmp, VImp, AEfficiencyPTCCEC listed
FS-6400A-P-x400 W216.102.51176.102.27≈15.9%367 WOct 21, 2021
FS-6405A-P-x405 W216.802.52177.202.29≈16.1%372 WOct 21, 2021
FS-6410A-P-x410 W217.402.52178.302.30≈16.3%377 WOct 21, 2021
FS-6415A-P-x415 W218.102.53179.302.31≈16.5%381 WOct 21, 2021
FS-6420A-P-x420 W218.102.53179.302.31≈16.7%386 WOct 21, 2021
FS-6425A-P-x425 W218.902.54181.502.34≈16.9%391 WOct 21, 2021
FS-6430A-P-x430 W219.202.54182.602.36≈17.1%396 WOct 21, 2021
FS-6435A-P-x435 W219.602.55183.602.37≈17.3%400 WOct 21, 2021
FS-6440A-P-x440 W220.002.56184.702.38≈17.5%405 WOct 21, 2021
FS-6445A-P-x445 W220.402.56185.702.40≈17.7%410 WOct 21, 2021
FS-6450A-P-x450 W221.102.57186.802.41≈17.9%414 WOct 21, 2021
FS-6455A-P-x455 W222.002.58187.802.42≈18.1%419 WOct 21, 2021
FS-6460A-P-x460 W222.902.59188.802.44≈18.3%424 WOct 21, 2021
≈ efficiency = Pmax ÷ CEC-listed area 2.52 m².

Heat & cold behaviour

CEC PV Module List (Oct 7, 2026) · Cali-Graf calculation
CEC listing test
Pmax coefficient γ−0.307 %/°C
Voc coefficient β−0.282 %/°C
Isc coefficient α+0.056 %/°C
Operating cell temperatureNOCT 50.7 °C
Vmp coefficient ≈ γ − α (CEC); used only for the hot-roof voltage estimate.

Away from lab conditions — CEC listing test points

ClassPmax at NOCTVmp × Imp at NOCTPmax at 200 W/m²Low-light efficiency vs STC
400 W306.6 W162.7 V × 1.88 A82.5 W103%
405 W311.3 W163.72 V × 1.9 A83.8 W103%
410 W314.6 W164.74 V × 1.91 A84.6 W103%
415 W317.7 W165.66 V × 1.92 A85.5 W103%
420 W317.7 W165.66 V × 1.92 A85.5 W102%
425 W325.8 W167.69 V × 1.94 A87.7 W103%
430 W330.6 W168.71 V × 1.96 A88.9 W103%
435 W333.8 W169.63 V × 1.97 A89.8 W103%
440 W337.2 W170.65 V × 1.98 A90.7 W103%
445 W341.9 W171.57 V × 1.99 A92 W103%
450 W345.3 W172.59 V × 2 A92.9 W103%
455 W348.6 W173.51 V × 2.01 A93.8 W103%
460 W353.4 W174.44 V × 2.03 A95.1 W103%
Pmax = Vmp × Imp from the CEC listing; low-light efficiency = Pmax at 200 W/m² ÷ (20% of STC Pmax).

Independent reliability testing

Kiwa PVEL Scorecard
2023
PVEL Top Performer
closely related product name
5
Tests passed as Top Performer
DH, LID+LETID, MSS, PID, TC
5
PVEL Scorecards
First Solar named Top Performer, 2018–2023

PVEL Top Performer tests

YearProductTests
2023FS-6xxxA-P (closely related product name)DHLID+LETIDMSSPIDTC

Tested bill of materials

Details describe the tested sample, not every module of the series.

Inverter compatibility & string sizing

CEC PV Module List (Oct 7, 2026) · Cali-Graf calculation · NLR PVWatts v8 · inverter datasheets · NLR SAM inverter library · CEC Grid Support Inverter List (Oct 7, 2026)
233.4 V
Voc when cold
per panel
150.1 V
Vmp when hot
per panel
2
Max panels / string
max DC 600 V
1
Min panels / string
MPPT from 60 V
Defaults come from NLR TMY weather (coldest hour, hottest modeled cell). Code calculations (NEC 690.7) use the ASHRAE extreme annual minimum, which is usually colder — enter it above. β is the CEC-measured coefficient; NEC 690.7 calculations use the datasheet value.

String inverters most named in SoCal permits

InverterMax DC inputMPPTWindow sourcePanels per string
Tesla 1538000-xx-y600 V60–480 Vdatasheet1–2
Solis (Ginlong) S6-EH1P10K-H-US600 V80–520 Vdatasheet1–2
Solis (Ginlong) Solis-1P7.6K-4G-US600 V100–500 Vdatasheet1–2
Qcells Q.VOLT H7.6SX498 V234–498 VCEC test window2–2

Microinverters (one per panel)

MicroinverterRecommended module powerMax DC inputMPPTVoc cold / Vmp hotCheckDC/AC
Enphase IQ8PLUS-72-2-US235–440 W60 V29–45 V233.4 / 150.1 V✗ Not allowed: cold Voc above max input1.48
Enphase IQ8X-80-M-US320–540 W79.5 V43–60 V233.4 / 150.1 V✗ Not allowed: cold Voc above max input1.13
APsystems (Alt Power System) DS3-L265–570 W60 V28–45 V233.4 / 150.1 V✗ Not allowed: cold Voc above max input0.55
Enphase IQ8M-72-2-US260–460 W60 V30–45 V233.4 / 150.1 V✗ Not allowed: cold Voc above max input1.32
Enphase IQ8A-72-2-US295–500 W60 V32–45 V233.4 / 150.1 V✗ Not allowed: cold Voc above max input1.23
Voltage check against the microinverter datasheets — confirm the pairing on the manufacturer’s module compatibility list. Rows appear only when the panel’s power is inside the microinverter’s recommended module power range.
SolarEdge and other optimizer-based systems size strings by the optimizer rules — use the manufacturer’s designer. Reference inverters: most named in SoCal permits since Oct 2024.

Expected production in Southern California

NLR PVWatts v8 · Cali-Graf calculation
CitykWh / kW / yrkWh / panel / yrkWh / system / yrSun, kWh/m²/day
Los Angeles1,67672111,5316.08
Palmdale1,83578912,6256.69
Chula Vista1,69672911,6686.11
Huntington Beach1,64370611,3045.89
Riverside1,69672911,6686.21
Santa Clarita1,72474111,8616.28
753Jan753Feb967Mar1,068Apr1,055May1,121Jun1,181Jul1,194Aug1,044Sep921Oct792Nov685DeckWh per month · Los Angeles
Estimate for comparison, not a quote: shading, roof orientation and local losses change real output. Roof mount, 20° tilt, south, 14% system losses.

About First Solar

CEC PV Module List (Oct 7, 2026) · Kiwa PVEL Scorecard

Other series by SoCal permits

FS-6xxx-P-BFS-6xxx-P-B-2FS-6xxxA-P-BFS-6xxxA-P-B-2FS-7xxxA-FT1FS-7xxxA-TR1

Questions & answers

How efficient is the First Solar FS-6430A-P-x?

Calculated from the panel area (2.52 m²): about 17.1% for the 430 W class. 430 W over 2.52 m² equals about 171 W per square meter.

How much energy does one panel produce in Los Angeles or Palmdale?

PVWatts v8 with typical-year weather gives about 721 kWh per year per 430 W panel in Los Angeles and about 789 kWh in Palmdale (20° roof, facing south, 14% system losses).

How much power does it lose on a hot roof?

With γ = −0.307 %/°C, at a 77 °C cell temperature (hottest modeled hour in Palmdale) output is about 15.9% below the STC rating.

How many panels fit on one string?

With the Tesla 1538000-xx-y (max DC 600 V, MPPT from 60 V, datasheet) in Los Angeles the calculator gives 1–2 panels per string (Voc at 2 °C = 233.4 V, Vmp at 74 °C cell = 150.1 V). Final design must follow the inverter manual and NEC 690.7.

Has this panel been reliability-tested?

FS-6xxxA-P was a PVEL Top Performer in 2023 (DH, LID+LETID, MSS, PID, TC) — a closely related product name.

Sources

  1. California Energy Commission — Solar Equipment Lists, PV Module List, Inverter List (snapshot Oct 7, 2026).
  2. Kiwa PVEL — PV Module Reliability Scorecard, Top Performer lists 2018–2023.
  3. NLR (formerly NREL) — System Advisor Model CEC inverter library (version 2026.7.3).
  4. NLR (formerly NREL) — PVWatts v8, NSRDB PSM v3 typical-year weather for Los Angeles, Palmdale, Chula Vista, Huntington Beach, Riverside, Santa Clarita.
  5. Inverter datasheets — APsystems (Alt Power System), Enphase, Solis (Ginlong), Tesla (manufacturer documents).
  6. Cali-Graf calculations — formulas and inputs are shown next to each calculated value (efficiency from area, temperature-corrected voltages, string sizing, energy estimates).