264 cells. Power classes 400–460 W in the CEC list.
| Model | Pmax | Voc, V | Isc, A | Vmp, V | Imp, A | Efficiency | PTC | CEC listed |
|---|---|---|---|---|---|---|---|---|
| FS-6400-P | 400 W | 216.10 | 2.51 | 176.10 | 2.27 | ≈15.9% | 374 W | Oct 3, 2022 |
| FS-6405-P | 405 W | 216.80 | 2.52 | 177.20 | 2.29 | ≈16.1% | 379 W | Oct 3, 2022 |
| FS-6410-P | 410 W | 217.40 | 2.52 | 178.30 | 2.30 | ≈16.3% | 384 W | Oct 3, 2022 |
| FS-6415-P | 415 W | 218.10 | 2.53 | 179.30 | 2.31 | ≈16.5% | 388 W | Oct 3, 2022 |
| FS-6420-P | 420 W | 218.10 | 2.53 | 179.30 | 2.31 | ≈16.7% | 393 W | Oct 3, 2022 |
| FS-6425-P | 425 W | 218.90 | 2.54 | 181.50 | 2.34 | ≈16.9% | 398 W | Oct 3, 2022 |
| FS-6430-P | 430 W | 219.20 | 2.54 | 182.60 | 2.36 | ≈17.1% | 403 W | Oct 3, 2022 |
| FS-6435-P | 435 W | 219.60 | 2.55 | 183.60 | 2.37 | ≈17.3% | 408 W | Oct 3, 2022 |
| FS-6440-P | 440 W | 220.00 | 2.56 | 184.70 | 2.38 | ≈17.5% | 412 W | Oct 3, 2022 |
| FS-6445-P | 445 W | 220.40 | 2.56 | 185.70 | 2.40 | ≈17.7% | 417 W | Oct 3, 2022 |
| FS-6450-P | 450 W | 221.10 | 2.57 | 186.80 | 2.41 | ≈17.9% | 422 W | Oct 3, 2022 |
| FS-6455-P | 455 W | 222.00 | 2.58 | 187.80 | 2.42 | ≈18.1% | 427 W | Oct 3, 2022 |
| FS-6460-P | 460 W | 222.90 | 2.59 | 188.80 | 2.44 | ≈18.3% | 432 W | Oct 3, 2022 |
| CEC listing test | |
|---|---|
| Pmax coefficient γ | −0.279 %/°C |
| Voc coefficient β | −0.271 %/°C |
| Isc coefficient α | +0.053 %/°C |
| Operating cell temperature | NOCT 47.3 °C |
| Class | Pmax at NOCT | Vmp × Imp at NOCT | Pmax at 200 W/m² | Low-light efficiency vs STC |
|---|---|---|---|---|
| 400 W | 317.9 W | 167.74 V × 1.9 A | 81.8 W | 102% |
| 405 W | 322.7 W | 168.79 V × 1.91 A | 83.1 W | 103% |
| 410 W | 326.1 W | 169.83 V × 1.92 A | 83.9 W | 102% |
| 415 W | 329.4 W | 170.79 V × 1.93 A | 84.8 W | 102% |
| 420 W | 329.4 W | 170.79 V × 1.93 A | 84.8 W | 101% |
| 425 W | 337.7 W | 172.88 V × 1.95 A | 86.9 W | 102% |
| 430 W | 342.7 W | 173.93 V × 1.97 A | 88.2 W | 103% |
| 435 W | 346 W | 174.88 V × 1.98 A | 89.1 W | 102% |
| 440 W | 349.6 W | 175.93 V × 1.99 A | 90 W | 102% |
| 445 W | 354.4 W | 176.88 V × 2 A | 91.2 W | 103% |
| 450 W | 358 W | 177.93 V × 2.01 A | 92.2 W | 102% |
| 455 W | 361.4 W | 178.88 V × 2.02 A | 93 W | 102% |
| 460 W | 366.3 W | 179.84 V × 2.04 A | 94.3 W | 103% |
| Inverter | Max DC input | MPPT | Window source | Panels per string |
|---|---|---|---|---|
| Tesla 1538000-xx-y | 600 V | 60–480 V | datasheet | 1–2 |
| Solis (Ginlong) S6-EH1P10K-H-US | 600 V | 80–520 V | datasheet | 1–2 |
| Solis (Ginlong) Solis-1P7.6K-4G-US | 600 V | 100–500 V | datasheet | 1–2 |
| Qcells Q.VOLT H7.6SX | 498 V | 234–498 V | CEC test window | 2–2 |
| Microinverter | Recommended module power | Max DC input | MPPT | Voc cold / Vmp hot | Check | DC/AC |
|---|---|---|---|---|---|---|
| Enphase IQ8PLUS-72-2-US | 235–440 W | 60 V | 29–45 V | 232.9 / 152.9 V | ✗ Not allowed: cold Voc above max input | 1.48 |
| Enphase IQ8X-80-M-US | 320–540 W | 79.5 V | 43–60 V | 232.9 / 152.9 V | ✗ Not allowed: cold Voc above max input | 1.13 |
| APsystems (Alt Power System) DS3-L | 265–570 W | 60 V | 28–45 V | 232.9 / 152.9 V | ✗ Not allowed: cold Voc above max input | 0.55 |
| Enphase IQ8M-72-2-US | 260–460 W | 60 V | 30–45 V | 232.9 / 152.9 V | ✗ Not allowed: cold Voc above max input | 1.32 |
| Enphase IQ8A-72-2-US | 295–500 W | 60 V | 32–45 V | 232.9 / 152.9 V | ✗ Not allowed: cold Voc above max input | 1.23 |
| City | kWh / kW / yr | kWh / panel / yr | kWh / system / yr | Sun, kWh/m²/day |
|---|---|---|---|---|
| Los Angeles | 1,676 | 721 | 11,531 | 6.08 |
| Palmdale | 1,835 | 789 | 12,625 | 6.69 |
| Chula Vista | 1,696 | 729 | 11,668 | 6.11 |
| Huntington Beach | 1,643 | 706 | 11,304 | 5.89 |
| Riverside | 1,696 | 729 | 11,668 | 6.21 |
| Santa Clarita | 1,724 | 741 | 11,861 | 6.28 |
Calculated from the panel area (2.52 m²): about 17.1% for the 430 W class. 430 W over 2.52 m² equals about 171 W per square meter.
PVWatts v8 with typical-year weather gives about 721 kWh per year per 430 W panel in Los Angeles and about 789 kWh in Palmdale (20° roof, facing south, 14% system losses).
With γ = −0.279 %/°C, at a 77 °C cell temperature (hottest modeled hour in Palmdale) output is about 14.5% below the STC rating.
With the Tesla 1538000-xx-y (max DC 600 V, MPPT from 60 V, datasheet) in Los Angeles the calculator gives 1–2 panels per string (Voc at 2 °C = 232.9 V, Vmp at 74 °C cell = 152.9 V). Final design must follow the inverter manual and NEC 690.7.
This exact series is not in published PVEL Top Performer tables; First Solar was named a Top Performer in 5 Scorecards (2018–2023).