EMMVEE Photovoltaic Power E565HCBT144-T

144 half-cut cells, bifacial, transparent backsheet. Power classes 550–580 W in the CEC list.

CEC listed · Nov 12, 2024UL 61730BifacialPVEL Top Performer 2025
Power class
  • Power (STC)565 WCEC nameplate
  • Efficiency≈22.1%calculated from area
  • %/°C Pmax−0.284CEC listing test
  • PTC / STC94.5%PTC 534 W (CEC)

Power classes

CEC PV Module List (Oct 7, 2026) · Cali-Graf calculation · 7 models
ModelPmaxVoc, VIsc, AVmp, VImp, AEfficiencyPTCCEC listed
E550HCBT144-T550 W50.2714.0141.5813.23≈21.5%520 WNov 12, 2024
E555HCBT144-T555 W50.4714.0741.7713.29≈21.7%524 WNov 12, 2024
E560HCBT144-T560 W50.6714.1341.9513.35≈21.9%529 WNov 12, 2024
E565HCBT144-T565 W50.8714.1942.1413.41≈22.1%534 WNov 12, 2024
E570HCBT144-T570 W51.0714.2542.2913.48≈22.3%539 WNov 12, 2024
E575HCBT144-T575 W51.2714.3142.4413.55≈22.5%544 WNov 12, 2024
E580HCBT144-T580 W51.4714.3742.5913.62≈22.7%548 WNov 12, 2024
≈ efficiency = Pmax ÷ CEC-listed area 2.56 m².

Build & dimensions

CEC PV Module List (Oct 7, 2026)

Heat & cold behaviour

CEC PV Module List (Oct 7, 2026) · Cali-Graf calculation
CEC listing test
Pmax coefficient γ−0.284 %/°C
Voc coefficient β−0.235 %/°C
Isc coefficient α+0.044 %/°C
Operating cell temperatureNOCT 45.8 °C
Vmp coefficient ≈ γ − α (CEC); used only for the hot-roof voltage estimate.

Away from lab conditions — CEC listing test points

ClassPmax at NOCTVmp × Imp at NOCTPmax at 200 W/m²Low-light efficiency vs STC
550 W407.4 W38.16 V × 10.68 A107.9 W98%
555 W411.1 W38.34 V × 10.72 A108.9 W98%
560 W414.8 W38.5 V × 10.77 A109.9 W98%
565 W418.5 W38.68 V × 10.82 A110.9 W98%
570 W422.2 W38.81 V × 10.88 A111.9 W98%
575 W425.9 W38.95 V × 10.93 A112.8 W98%
580 W429.6 W39.09 V × 10.99 A113.8 W98%
Pmax = Vmp × Imp from the CEC listing; low-light efficiency = Pmax at 200 W/m² ÷ (20% of STC Pmax).

Independent reliability testing

Kiwa PVEL Scorecard
2024, 2025
PVEL Top Performer
this series
1
Tests passed as Top Performer
LID+LETID
4
PVEL Scorecards
EMMVEE Photovoltaic Power named Top Performer, 2023–2026

PVEL Top Performer tests

YearProductTests
2025ExxxHCBT144-TLID+LETID
2024ExxxHCBT144 (closely related product name)LID+LETID

Tested bill of materials

Details describe the tested sample, not every module of the series.

Inverter compatibility & string sizing

CEC PV Module List (Oct 7, 2026) · Cali-Graf calculation · NLR PVWatts v8 · inverter datasheets · NLR SAM inverter library · CEC Grid Support Inverter List (Oct 7, 2026)
53.6 V
Voc when cold
per panel
35.4 V
Vmp when hot
per panel
11
Max panels / string
max DC 600 V
2
Min panels / string
MPPT from 60 V
Defaults come from NLR TMY weather (coldest hour, hottest modeled cell). Code calculations (NEC 690.7) use the ASHRAE extreme annual minimum, which is usually colder — enter it above. β is the CEC-measured coefficient; NEC 690.7 calculations use the datasheet value.

String inverters most named in SoCal permits

InverterMax DC inputMPPTWindow sourcePanels per string
Tesla 1538000-xx-y600 V60–480 Vdatasheet2–11
Solis (Ginlong) S6-EH1P10K-H-US600 V80–520 Vdatasheet3–11
Solis (Ginlong) Solis-1P7.6K-4G-US600 V100–500 Vdatasheet3–11
Qcells Q.VOLT H7.6SX498 V234–498 VCEC test window7–9

Microinverters (one per panel)

MicroinverterRecommended module powerMax DC inputMPPTVoc cold / Vmp hotCheckDC/AC
APsystems (Alt Power System) DS3-L265–570 W60 V28–45 V53.6 / 35.4 V✓ Within range0.72
Voltage check against the microinverter datasheets — confirm the pairing on the manufacturer’s module compatibility list. Rows appear only when the panel’s power is inside the microinverter’s recommended module power range.
SolarEdge and other optimizer-based systems size strings by the optimizer rules — use the manufacturer’s designer. Reference inverters: most named in SoCal permits since Oct 2024.

Expected production in Southern California

NLR PVWatts v8 · Cali-Graf calculation
CitykWh / kW / yrkWh / panel / yrkWh / system / yrSun, kWh/m²/day
Los Angeles1,67694711,3636.08
Palmdale1,8351,03712,4416.69
Chula Vista1,69695811,4996.11
Huntington Beach1,64392811,1405.89
Riverside1,69695811,4996.21
Santa Clarita1,72497411,6896.28
742Jan742Feb953Mar1,052Apr1,039May1,104Jun1,163Jul1,177Aug1,029Sep908Oct780Nov675DeckWh per month · Los Angeles
Estimate for comparison, not a quote: shading, roof orientation and local losses change real output. Roof mount, 20° tilt, south, 14% system losses.

Compare with similar 565 W panels

CEC PV Module List (Oct 7, 2026) · LONGi datasheet · Kiwa PVEL Scorecard · building permits
PanelPmaxEfficiencyγ Pmax (CEC)Voc, VIsc, APVEL (product / brand)SoCal permits (series)
EMMVEE Photovoltaic Power E565HCBT144-T565 W≈22.1%−0.28450.8714.19product 2025—
LONGi LR5-72HBD-565M565 W≈22.1%−0.35450.2514.16product 20261
ZNShine Solar ZXM7-UHLDD144-565/N565 W≈22.1%−0.30250.914.17product 2024, 2025, 20261
VSUN (Vietnam Sunergy) VSUN570N-144MH570 W≈22.1%−0.30951.5813.72brand 6× (2021–2026)1
Same fields from the same sources for every row; ≈ efficiency is calculated from the listed area. Comparable series: other brands, same product group, power range covering this class.

About EMMVEE Photovoltaic Power

CEC PV Module List (Oct 7, 2026) · Kiwa PVEL Scorecard

Other series by SoCal permits

ExxxHCBG132-TExxxHCBG144-TExxxHCM120-BTExxxHCMW144-TExxxHCBG144ExxxHCM120-B

Questions & answers

How efficient is the EMMVEE Photovoltaic Power E565HCBT144-T?

Calculated from the panel area (2.56 m²): about 22.1% for the 565 W class. 565 W over 2.56 m² equals about 221 W per square meter.

How much energy does one panel produce in Los Angeles or Palmdale?

PVWatts v8 with typical-year weather gives about 947 kWh per year per 565 W panel in Los Angeles and about 1,037 kWh in Palmdale (20° roof, facing south, 14% system losses).

How much power does it lose on a hot roof?

With γ = −0.284 %/°C, at a 77 °C cell temperature (hottest modeled hour in Palmdale) output is about 14.7% below the STC rating.

How many panels fit on one string?

With the Tesla 1538000-xx-y (max DC 600 V, MPPT from 60 V, datasheet) in Los Angeles the calculator gives 2–11 panels per string (Voc at 2 °C = 53.6 V, Vmp at 74 °C cell = 35.4 V). Final design must follow the inverter manual and NEC 690.7.

Does it work with APsystems (Alt Power System) DS3-L microinverters?

Voltage check against the APsystems (Alt Power System) datasheet: Voc when cold 53.6 V vs max input 60 V; Vmp when hot 35.4 V vs MPPT low 28 V; recommended module power 265–570 W. Confirm on the microinverter maker’s compatibility list.

Is it bifacial?

Yes. Rear gain depends on mounting height and ground reflectance.

Has this panel been reliability-tested?

ExxxHCBT144-T was a PVEL Top Performer in 2025 (LID+LETID).

Sources

  1. California Energy Commission — Solar Equipment Lists, PV Module List, Inverter List (snapshot Oct 7, 2026).
  2. LONGi — manufacturer datasheet “LR5-72HBD Suitable for distributed projects Advanced module technology delivers superior”.
  3. Kiwa PVEL — PV Module Reliability Scorecard, Top Performer lists 2023–2026.
  4. NLR (formerly NREL) — System Advisor Model CEC module and inverter libraries (version 2026.7.3).
  5. NLR (formerly NREL) — PVWatts v8, NSRDB PSM v3 typical-year weather for Los Angeles, Palmdale, Chula Vista, Huntington Beach, Riverside, Santa Clarita.
  6. Inverter datasheets — APsystems (Alt Power System), Solis (Ginlong), Tesla (manufacturer documents).
  7. Building permits — Southern California permit portals. Equipment matched from permit descriptions.
  8. Cali-Graf calculations — formulas and inputs are shown next to each calculated value (efficiency from area, temperature-corrected voltages, string sizing, energy estimates).