Chint New Energy CHSM66N-HC 675

132 half-cut cells. Power classes 655–695 W in the CEC list.

CEC listed · Feb 1, 2023UL 61730
Power class
  • Power (STC)675 WCEC nameplate
  • Efficiency≈21.7%calculated from area
  • %/°C Pmax−0.303CEC listing test
  • PTC / STC94.3%PTC 637 W (CEC)

Power classes

CEC PV Module List (Oct 7, 2026) · Cali-Graf calculation · 9 models
ModelPmaxVoc, VIsc, AVmp, VImp, AEfficiencyPTCCEC listed
CHSM66N-HC-655655 W46.3617.6438.4717.03≈21.1%617 WFeb 1, 2023
CHSM66N-HC-660660 W46.5617.7238.6417.08≈21.2%622 WFeb 1, 2023
CHSM66N-HC-665665 W46.7617.8038.8117.14≈21.4%627 WFeb 1, 2023
CHSM66N-HC-670670 W46.9617.8838.9717.19≈21.5%632 WFeb 1, 2023
CHSM66N-HC-675675 W47.1717.9639.1417.24≈21.7%637 WFeb 1, 2023
CHSM66N-HC-680680 W47.3718.0339.3117.30≈21.9%642 WFeb 1, 2023
CHSM66N-HC-685685 W47.5718.1139.4817.35≈22.0%646 WFeb 1, 2023
CHSM66N-HC-690690 W47.7818.1939.6517.40≈22.2%651 WFeb 1, 2023
CHSM66N-HC-695695 W47.9818.2739.8217.46≈22.3%656 WFeb 1, 2023
≈ efficiency = Pmax ÷ CEC-listed area 3.11 m².

Build & dimensions

CEC PV Module List (Oct 7, 2026)

Heat & cold behaviour

CEC PV Module List (Oct 7, 2026) · Cali-Graf calculation
CEC listing test
Pmax coefficient γ−0.303 %/°C
Voc coefficient β−0.241 %/°C
Isc coefficient α+0.039 %/°C
Operating cell temperatureNOCT 45 °C
Vmp coefficient ≈ γ − α (CEC); used only for the hot-roof voltage estimate.

Away from lab conditions — CEC listing test points

ClassPmax at NOCTVmp × Imp at NOCTPmax at 200 W/m²Low-light efficiency vs STC
655 W487.8 W36.29 V × 13.44 A128.5 W98%
660 W491.4 W36.45 V × 13.48 A129.5 W98%
665 W495.3 W36.61 V × 13.53 A130.5 W98%
670 W498.8 W36.76 V × 13.57 A131.4 W98%
675 W502.4 W36.92 V × 13.61 A132.4 W98%
680 W506.4 W37.08 V × 13.66 A133.4 W98%
685 W510 W37.24 V × 13.69 A134.4 W98%
690 W513.7 W37.4 V × 13.73 A135.3 W98%
695 W517.7 W37.56 V × 13.78 A136.4 W98%
Pmax = Vmp × Imp from the CEC listing; low-light efficiency = Pmax at 200 W/m² ÷ (20% of STC Pmax).

Inverter compatibility & string sizing

CEC PV Module List (Oct 7, 2026) · Cali-Graf calculation · NLR PVWatts v8 · inverter datasheets · NLR SAM inverter library · CEC Grid Support Inverter List (Oct 7, 2026)
49.8 V
Voc when cold
per panel
32.6 V
Vmp when hot
per panel
12
Max panels / string
max DC 600 V
2
Min panels / string
MPPT from 60 V
Defaults come from NLR TMY weather (coldest hour, hottest modeled cell). Code calculations (NEC 690.7) use the ASHRAE extreme annual minimum, which is usually colder — enter it above. β is the CEC-measured coefficient; NEC 690.7 calculations use the datasheet value.

String inverters most named in SoCal permits

InverterMax DC inputMPPTWindow sourcePanels per string
Tesla 1538000-xx-y600 V60–480 Vdatasheet2–12
Solis (Ginlong) S6-EH1P10K-H-US600 V80–520 Vdatasheet3–12
Solis (Ginlong) Solis-1P7.6K-4G-US600 V100–500 Vdatasheet4–12
Qcells Q.VOLT H7.6SX498 V234–498 VCEC test window8–10

Microinverters (one per panel)

No microinverter in the reference set lists this power class in its recommended module power range.
Voltage check against the microinverter datasheets — confirm the pairing on the manufacturer’s module compatibility list. Rows appear only when the panel’s power is inside the microinverter’s recommended module power range.
SolarEdge and other optimizer-based systems size strings by the optimizer rules — use the manufacturer’s designer. Reference inverters: most named in SoCal permits since Oct 2024.

Expected production in Southern California

NLR PVWatts v8 · Cali-Graf calculation
CitykWh / kW / yrkWh / panel / yrkWh / system / yrSun, kWh/m²/day
Los Angeles1,6761,13111,3136.08
Palmdale1,8351,23912,3866.69
Chula Vista1,6961,14511,4486.11
Huntington Beach1,6431,10911,0905.89
Riverside1,6961,14511,4486.21
Santa Clarita1,7241,16411,6376.28
738Jan739Feb948Mar1,048Apr1,035May1,100Jun1,158Jul1,172Aug1,025Sep904Oct777Nov672DeckWh per month · Los Angeles
Estimate for comparison, not a quote: shading, roof orientation and local losses change real output. Roof mount, 20° tilt, south, 14% system losses.

Compare with similar 675 W panels

CEC PV Module List (Oct 7, 2026) · Kiwa PVEL Scorecard · Waaree datasheet
PanelPmaxEfficiencyγ Pmax (CEC)Voc, VIsc, A
Chint New Energy CHSM66N-HC 675675 W≈21.7%−0.30347.1717.96
Canadian Solar CS7N-670MB-AG670 W≈21.8%−0.39045.818.55
Waaree BiN-03-680680 W≥21.9%−0.30247.5518.16
Same fields from the same sources for every row; ≈ efficiency is calculated from the listed area. Comparable series: other brands, same product group, power range covering this class.

Questions & answers

How efficient is the Chint New Energy CHSM66N-HC 675?

Calculated from the panel area (3.11 m²): about 21.7% for the 675 W class. 675 W over 3.11 m² equals about 217 W per square meter.

How much energy does one panel produce in Los Angeles or Palmdale?

PVWatts v8 with typical-year weather gives about 1,131 kWh per year per 675 W panel in Los Angeles and about 1,239 kWh in Palmdale (20° roof, facing south, 14% system losses).

How much power does it lose on a hot roof?

With γ = −0.303 %/°C, at a 77 °C cell temperature (hottest modeled hour in Palmdale) output is about 15.7% below the STC rating.

How many panels fit on one string?

With the Tesla 1538000-xx-y (max DC 600 V, MPPT from 60 V, datasheet) in Los Angeles the calculator gives 2–12 panels per string (Voc at 2 °C = 49.8 V, Vmp at 74 °C cell = 32.6 V). Final design must follow the inverter manual and NEC 690.7.

Sources

  1. California Energy Commission — Solar Equipment Lists, PV Module List, Inverter List (snapshot Oct 7, 2026).
  2. Waaree — datasheet ELITE SERIES BiN-03.
  3. Kiwa PVEL — PV Module Reliability Scorecard, Top Performer lists.
  4. NLR (formerly NREL) — System Advisor Model CEC inverter library (version 2026.7.3).
  5. NLR (formerly NREL) — PVWatts v8, NSRDB PSM v3 typical-year weather for Los Angeles, Palmdale, Chula Vista, Huntington Beach, Riverside, Santa Clarita.
  6. Inverter datasheets — Solis (Ginlong), Tesla (manufacturer documents).
  7. Cali-Graf calculations — formulas and inputs are shown next to each calculated value (efficiency from area, temperature-corrected voltages, string sizing, energy estimates).