Cali-GrafCali-Graf
Solar panelBoviet Solar

Boviet Solar BVM6612M-440S-H-HC

144 half-cut cells. Power classes 425–455 W in the CEC list.

CEC listed · Oct 12, 2020UL 61730
Power class
  • Power (STC)440 WCEC nameplate
  • Efficiency≈20.0%calculated from area
  • %/°C Pmax−0.364CEC listing test
  • PTC / STC93.7%PTC 412 W (CEC)

Power classes

CEC PV Module List (Oct 7, 2026) · Cali-Graf calculation · 7 models
ModelPmaxVoc, VIsc, AVmp, VImp, AEfficiencyPTCCEC listed
BVM6612M-425S-H-HC425 W48.1011.2839.7610.71≈19.3%398 WOct 12, 2020
BVM6612M-430S-H-HC430 W48.2511.3439.9610.78≈19.5%403 WOct 12, 2020
BVM6612M-435S-H-HC435 W48.4511.4240.1710.85≈19.8%408 WOct 12, 2020
BVM6612M-440S-H-HC440 W48.6011.4840.3710.92≈20.0%412 WOct 12, 2020
BVM6612M-445S-H-HC445 W48.8011.5540.5710.99≈20.2%417 WOct 12, 2020
BVM6612M-450S-H-HC450 W49.0511.6040.7611.06≈20.5%422 WOct 12, 2020
BVM6612M-455S-H-HC455 W49.2511.7140.8811.15≈20.7%427 WOct 12, 2020
≈ efficiency = Pmax ÷ CEC-listed area 2.2 m².

Build & dimensions

CEC PV Module List (Oct 7, 2026)

Heat & cold behaviour

CEC PV Module List (Oct 7, 2026) · Cali-Graf calculation
CEC listing test
Pmax coefficient γ−0.364 %/°C
Voc coefficient β−0.291 %/°C
Isc coefficient α+0.026 %/°C
Operating cell temperatureNOCT 42.9 °C
Vmp coefficient ≈ γ − α (CEC); used only for the hot-roof voltage estimate.

Away from lab conditions — CEC listing test points

ClassPmax at NOCTVmp × Imp at NOCTPmax at 200 W/m²Low-light efficiency vs STC
425 W316.1 W36.73 V × 8.61 A82.7 W97%
430 W319.7 W36.91 V × 8.66 A83.6 W97%
435 W323.5 W37.11 V × 8.72 A84.6 W97%
440 W327.2 W37.29 V × 8.77 A85.6 W97%
445 W330.9 W37.48 V × 8.83 A86.6 W97%
450 W334.6 W37.65 V × 8.89 A87.5 W97%
455 W338.3 W37.76 V × 8.96 A88.5 W97%
Pmax = Vmp × Imp from the CEC listing; low-light efficiency = Pmax at 200 W/m² ÷ (20% of STC Pmax).

Independent reliability testing

Kiwa PVEL Scorecard
2021, 2022, 2023
PVEL Top Performer
closely related product name
6
Tests passed as Top Performer
DH, LID+LETID, MSS, PAN, PID, TC
6
PVEL Scorecards
Boviet Solar named Top Performer, 2019–2024

PVEL Top Performer tests

YearProductTests
2021BVM6612M-xxxS-H-HC-BF-DG (closely related product name)LID+LETID
2022BVM6612M-xxxS-H-HC-BF-DG (closely related product name)DHLID+LETIDMSSPANPIDTC
2023BVM6612M-xxxS-H-HC-BF-DG (closely related product name)PID
2022BVM6612M-xxxS-H-HC-BF (closely related product name)LID+LETIDTC

Tested bill of materials

Details describe the tested sample, not every module of the series.

Inverter compatibility & string sizing

CEC PV Module List (Oct 7, 2026) · Cali-Graf calculation · NLR PVWatts v8 · inverter datasheets · NLR SAM inverter library · CEC Grid Support Inverter List (Oct 7, 2026)
51.9 V
Voc when cold
per panel
32.7 V
Vmp when hot
per panel
11
Max panels / string
max DC 600 V
2
Min panels / string
MPPT from 60 V
Defaults come from NLR TMY weather (coldest hour, hottest modeled cell). Code calculations (NEC 690.7) use the ASHRAE extreme annual minimum, which is usually colder — enter it above. β is the CEC-measured coefficient; NEC 690.7 calculations use the datasheet value.

String inverters most named in SoCal permits

InverterMax DC inputMPPTWindow sourcePanels per string
Tesla 1538000-xx-y600 V60–480 Vdatasheet2–11
Solis (Ginlong) S6-EH1P10K-H-US600 V80–520 Vdatasheet3–11
Solis (Ginlong) Solis-1P7.6K-4G-US600 V100–500 Vdatasheet4–11
Qcells Q.VOLT H7.6SX498 V234–498 VCEC test window8–9

Microinverters (one per panel)

MicroinverterRecommended module powerMax DC inputMPPTVoc cold / Vmp hotCheckDC/AC
Enphase IQ8PLUS-72-2-US235–440 W60 V29–45 V51.9 / 32.7 V✓ Within range1.52
Enphase IQ8X-80-M-US320–540 W79.5 V43–60 V51.9 / 32.7 V✗ Not a match: module voltage below MPPT range1.16
APsystems (Alt Power System) DS3-L265–570 W60 V28–45 V51.9 / 32.7 V✓ Within range0.56
Enphase IQ8M-72-2-US260–460 W60 V30–45 V51.9 / 32.7 V✓ Within range1.35
Enphase IQ8A-72-2-US295–500 W60 V32–45 V51.9 / 32.7 V✓ Within range1.26
Voltage check against the microinverter datasheets — confirm the pairing on the manufacturer’s module compatibility list. Rows appear only when the panel’s power is inside the microinverter’s recommended module power range.
SolarEdge and other optimizer-based systems size strings by the optimizer rules — use the manufacturer’s designer. Reference inverters: most named in SoCal permits since Oct 2024.

Expected production in Southern California

NLR PVWatts v8 · Cali-Graf calculation
CitykWh / kW / yrkWh / panel / yrkWh / system / yrSun, kWh/m²/day
Los Angeles1,67673711,7996.08
Palmdale1,83580712,9186.69
Chula Vista1,69674611,9406.11
Huntington Beach1,64372311,5675.89
Riverside1,69674611,9406.21
Santa Clarita1,72475912,1376.28
770Jan771Feb989Mar1,093Apr1,079May1,147Jun1,208Jul1,222Aug1,069Sep943Oct810Nov701DeckWh per month · Los Angeles
Estimate for comparison, not a quote: shading, roof orientation and local losses change real output. Roof mount, 20° tilt, south, 14% system losses.

Compare with similar 440 W panels

CEC PV Module List (Oct 7, 2026) · datasheets · Kiwa PVEL Scorecard · building permits
PanelPmaxEfficiencyγ Pmax (CEC)Voc, VIsc, AWarrantyPVEL (product / brand)SoCal permits (series)
Boviet Solar BVM6612M-440S-H-HC440 W≈20%−0.36448.611.48—brand 6×—
Qcells Q.TRON BLK M-G2+ 440440 W≥22.5%−0.27639.8813.925 / 25 yrbrand 11× (2016–2026)40
Silfab Solar SIL-440QD440 W≈22.6%−0.29438.9714.2525 / 30 yrbrand 7× (2017–2025)39
Hyundai Energy Solutions HiN-T440NF(BK)440 W≈22.7%−0.29838.814.3925 / 30 yrbrand 5× (2017–2025)37
Same fields from the same sources for every row; ≈ efficiency is calculated from the listed area. Comparable series: other brands, same product group, power range covering this class.

About Boviet Solar

CEC PV Module List (Oct 7, 2026) · Kiwa PVEL Scorecard · building permits

Other series by SoCal permits

BVM6610M-xxxS-H-HC-BF · 1BVM7612M-xxx-H-HC-BFBVM7612M-xxx-H-HC-BF-DGBVM7613M-xxx-H-HC-BFBVM7613M-xxx-H-HC-BF-DGBVM7610M-xxx-H-HC-BF

Questions & answers

How efficient is the Boviet Solar BVM6612M-440S-H-HC?

Calculated from the panel area (2.2 m²): about 20% for the 440 W class. 440 W over 2.2 m² equals about 200 W per square meter.

How much energy does one panel produce in Los Angeles or Palmdale?

PVWatts v8 with typical-year weather gives about 737 kWh per year per 440 W panel in Los Angeles and about 807 kWh in Palmdale (20° roof, facing south, 14% system losses).

How much power does it lose on a hot roof?

With γ = −0.364 %/°C, at a 77 °C cell temperature (hottest modeled hour in Palmdale) output is about 18.9% below the STC rating.

How many panels fit on one string?

With the Tesla 1538000-xx-y (max DC 600 V, MPPT from 60 V, datasheet) in Los Angeles the calculator gives 2–11 panels per string (Voc at 2 °C = 51.9 V, Vmp at 74 °C cell = 32.7 V). Final design must follow the inverter manual and NEC 690.7.

Does it work with Enphase IQ8PLUS-72-2-US microinverters?

Voltage check against the Enphase datasheet: Voc when cold 51.9 V vs max input 60 V; Vmp when hot 32.7 V vs MPPT low 29 V; recommended module power 235–440 W. Confirm on the microinverter maker’s compatibility list.

Has this panel been reliability-tested?

BVM6612M-xxxS-H-HC-BF-DG was a PVEL Top Performer in 2021, 2022, 2023 (DH, LID+LETID, MSS, PAN, PID, TC) — a closely related product name.

Sources

  1. California Energy Commission — Solar Equipment Lists, PV Module List, Inverter List (snapshot Oct 7, 2026).
  2. Qcells — manufacturer datasheet “Q.TRON BLK M-G2+ SERIES 415–440 Wp”.
  3. Silfab Solar — datasheet NTC SIL-420 QD CELL TECHNOLOGY.
  4. Hyundai Energy Solutions — datasheet [US] NF(BK)(HiN) Series (N TOPCon Bifacial) 435~445W.
  5. Kiwa PVEL — PV Module Reliability Scorecard, Top Performer lists 2019–2024.
  6. NLR (formerly NREL) — System Advisor Model CEC inverter library (version 2026.7.3).
  7. NLR (formerly NREL) — PVWatts v8, NSRDB PSM v3 typical-year weather for Los Angeles, Palmdale, Chula Vista, Huntington Beach, Riverside, Santa Clarita.
  8. Inverter datasheets — APsystems (Alt Power System), Enphase, Solis (Ginlong), Tesla (manufacturer documents).
  9. Building permits — Southern California permit portals. Equipment matched from permit descriptions.
  10. Cali-Graf calculations — formulas and inputs are shown next to each calculated value (efficiency from area, temperature-corrected voltages, string sizing, energy estimates).