CEC test DC voltages (min / nom / max)648 / 1,000 / 1,500 V
DC input at rated output (CEC test)837.6 kW
AC output (grid side)
CEC Grid Support Inverter List (Oct 7, 2026)
Rated AC power800 kW
CEC-measured continuous output814.2 kW
Grid voltage440 V
Phase3-phase 440 V
Efficiency
CEC Grid Support Inverter List (Oct 7, 2026) · NLR SAM inverter library
CEC weighted efficiency97.5%
Night-time standby (tare)91.4 W
Power to start converting1,992.1 W
CEC weighted efficiency is measured by an accredited lab at six power levels and three DC voltages — the number to compare between inverters.
Grid & smart-inverter certification
CEC Grid Support Inverter List (Oct 7, 2026)
UL 1741 SB (3rd ed.)No
UL 1741 SA (SA8–SA13)Yes — MET
Firmware tested (SA)APU V3130 APMC V2040
Volt-VAr with reactive power priority (SA13)Yes
Freq-Watt / Volt-Watt (SA14–15)Yes
Disable permit service / limit active power (SA17–18)No
CSIP (IEEE 2030.5) conformanceNo
Monitor key data & scheduling (Rule 21 Phase 3)No
CEC listedNov 12, 2020
CEC noteEfficiency data inclusive of transformer effect based on 1000 kVA Low-Voltage Dry-Type Distribution Transformers Table in DOE216.
UL 1741 SB is required for new interconnections in California (Rule 21) since 2026.
Panel compatibility & string sizing
NLR SAM inverter library · NLR PVWatts v8 · CEC PV Module List · Cali-Graf calculation
APS800-PV-1-440-5: max DC 1,500 V · MPPT 648–1,500 V (CEC test window)
Most-permitted panels in Southern California
Panel
Power
Voc cold
Vmp hot
Panels per string
Installed together
Qcells Q.PEAK DUO BLK ML-G10.C+ 410
410 W
48.1 V
30.6 V
22–31
—
Qcells Q.PEAK DUO BLK ML-G10+ 410
410 W
48.1 V
30.6 V
22–31
—
LONGi LR5-54HABB-400M
400 W
39.3 V
25.3 V
26–38
—
JA Solar JAM54S31-405/MR
405 W
39.4 V
25.5 V
26–38
—
Hyundai Solutions HiN-T440NF(BK)
440 W
40.9 V
27 V
24–36
—
Silfab Solar SIL-440QD
440 W
41.1 V
28 V
24–36
—
Qcells Q.TRON BLK M-G2+ 430
430 W
41.3 V
28 V
24–36
—
Qcells Q.TRON BLK M-G2.H+ 430
430 W
41.3 V
28 V
24–36
—
REC Group REC460AA Pure-RX
460 W
68.8 V
47.1 V
14–21
—
Elin (Sirius PV) ELNSM54M-HC-410
410 W
39.3 V
25.3 V
26–38
—
Qcells Q.TRON BLK M-G2.C+ 430
430 W
41.3 V
28 V
24–36
—
Tesla TSP-420
420 W
43.4 V
27.7 V
24–34
—
Voltage check only, from CEC panel data and NLR weather for the city. Final design must follow the inverter manual and NEC 690.7.
About WSTECH
CEC Grid Support Inverter List (Oct 7, 2026)
ManufacturerWSTECH
Listed in CEC asWSTECH GmbH
Models on CEC lists8
Other series
APSxxx-PV-1-480-5
Questions & answers
How efficient is the WSTECH APSxxx-PV-1-440-5?
The California Energy Commission lists a weighted efficiency of 97.5% for WSTECH APSxxx-PV-1-440-5 models, measured at six power levels and three DC voltages.
Is the WSTECH APSxxx-PV-1-440-5 certified to UL 1741 SB?
The CEC list does not show UL 1741 SB certification for these models.
What is the APS800-PV-1-440-5’s DC input voltage range?
CEC tested it at 648–1,500 V DC.
Sources
California Energy Commission — Grid Support Inverter List (solar and battery inverters), data as of Oct 7, 2026. Manufacturer-reported, confirmed by CEC against certificates and test reports.
NLR (formerly NREL) — System Advisor Model CEC inverter library (version 2026.7.3).
NLR (formerly NREL) — PVWatts v8, NSRDB PSM v3 typical-year weather for Los Angeles, Palmdale, Riverside, Santa Clarita, Chula Vista, Huntington Beach.
California Energy Commission — PV Module List (module electrical data for the compatibility check).
Cali-Graf calculations — formulas and inputs are shown next to each calculated value (efficiency from area, temperature-corrected voltages, string sizing, energy estimates).
Get your free estimate
Three fields, and Cali Energy calls back within 30 minutes during business hours.
Thanks!
We got your request and will call back within 30 minutes during business hours.