Cali-GrafCali-Graf
String inverterTMEIC

TMEIC PVU-L0840URN

String inverter. 1 model, 840 kW AC at 630 V.

UL 1741 SBCEC listed · Jul 1, 2024
  • Rated AC power840 kW
  • CEC weighted efficiency98.5%

DC input (PV side)

CEC Grid Support Inverter List (Oct 7, 2026) · NLR SAM inverter library

AC output (grid side)

CEC Grid Support Inverter List (Oct 7, 2026)

Efficiency

CEC Grid Support Inverter List (Oct 7, 2026) · NLR SAM inverter library
CEC weighted efficiency is measured by an accredited lab at six power levels and three DC voltages — the number to compare between inverters.

Grid & smart-inverter certification

CEC Grid Support Inverter List (Oct 7, 2026)
UL 1741 SB is required for new interconnections in California (Rule 21) since 2026.

Panel compatibility & string sizing

NLR SAM inverter library · NLR PVWatts v8 · CEC PV Module List · Cali-Graf calculation
PVU-L0840URN: max DC 1,200 V · MPPT 915–1,200 V (CEC test window)

Most-permitted panels in Southern California

PanelPowerVoc coldVmp hotPanels per stringInstalled together
Qcells Q.PEAK DUO BLK ML-G10.C+ 410410 W48.1 V30.6 Vno fit—
Qcells Q.PEAK DUO BLK ML-G10+ 410410 W48.1 V30.6 Vno fit—
LONGi LR5-54HABB-400M400 W39.3 V25.3 Vno fit—
JA Solar JAM54S31-405/MR405 W39.4 V25.5 Vno fit—
Hyundai Solutions HiN-T440NF(BK)440 W40.9 V27 Vno fit—
Silfab Solar SIL-440QD440 W41.1 V28 Vno fit—
Qcells Q.TRON BLK M-G2+ 430430 W41.3 V28 Vno fit—
Qcells Q.TRON BLK M-G2.H+ 430430 W41.3 V28 Vno fit—
REC Group REC460AA Pure-RX460 W68.8 V47.1 Vno fit—
Elin (Sirius PV) ELNSM54M-HC-410410 W39.3 V25.3 Vno fit—
Qcells Q.TRON BLK M-G2.C+ 430430 W41.3 V28 Vno fit—
Tesla TSP-420420 W43.4 V27.7 Vno fit—
Voltage check only, from CEC panel data and NLR weather for the city. Final design must follow the inverter manual and NEC 690.7.

About TMEIC

CEC Grid Support Inverter List (Oct 7, 2026)

Other series

PVU-LxxxxGR

Questions & answers

How efficient is the TMEIC PVU-LxxxxURN?

The California Energy Commission lists a weighted efficiency of 98.5% for TMEIC PVU-LxxxxURN models, measured at six power levels and three DC voltages.

Is the TMEIC PVU-LxxxxURN certified to UL 1741 SB?

Yes — the CEC Grid Support Inverter List shows UL 1741 SB for all models.

What is the PVU-L0840URN’s DC input voltage range?

CEC tested it at 915–1,200 V DC.

Sources

  1. California Energy Commission — Grid Support Inverter List (solar and battery inverters), data as of Oct 7, 2026. Manufacturer-reported, confirmed by CEC against certificates and test reports.
  2. NLR (formerly NREL) — System Advisor Model CEC inverter library (version 2026.7.3).
  3. NLR (formerly NREL) — PVWatts v8, NSRDB PSM v3 typical-year weather for Los Angeles, Palmdale, Riverside, Santa Clarita, Chula Vista, Huntington Beach.
  4. California Energy Commission — PV Module List (module electrical data for the compatibility check).
  5. Cali-Graf calculations — formulas and inputs are shown next to each calculated value (efficiency from area, temperature-corrected voltages, string sizing, energy estimates).