Cali-GrafCali-Graf
String inverterSolarEdge

SolarEdge SE50KUS

String inverter. 19 models, 9 kW–330 kW AC at 208 V / 480 V / 600 V / 690 V. used with power optimizers.

UL 1741 SB · 16 of 19 modelsCEC listed · Jul 1, 2017Rapid shutdownInstalled in 14 SoCal permits
Model
  • Rated AC power50 kW
  • CEC weighted efficiency97.0%

Models & power ratings

CEC Grid Support Inverter List (Oct 7, 2026) · NLR SAM inverter library · building permits · 19 models
ModelNominal ACGrid voltageCEC continuousRated AC (SAM)CEC weighted eff.DC test windowCEC listedUL 1741 SBIn permits
SE9KUS9 kW208 V8.96 kW8.96 kW96.5%384–504 VJul 1, 2017——
SE10KUS10 kW480 V9.85 kW9.85 kW98.0%100–962 VJul 1, 2017——
SE10KUS10 kW208 V10 kW10 kW97.0%400–600 VFeb 13, 2023SB—
SE14.4KUS14.4 kW208 V14.5 kW14.5 kW97.0%400–600 VJul 1, 2017SB1
SE17.3KUS17.3 kW208 V16.6 kW16.6 kW97.0%400–600 VAug 11, 2020SB2
SE20KUS20 kW480 V20.1 kW20.1 kW98.0%842–962 VJul 1, 2017——
SE30KUS30 kW480 V30.2 kW30.2 kW98.5%790–950 VJan 2, 2018SB1
SE33.3KUS33.3 kW480 V33.3 kW33.3 kW98.5%790–950 VJul 1, 2017SB—
SE40KUS40 kW480 V40.3 kW40.3 kW98.5%790–950 VAug 11, 2020SB2
SE43.2KUS43.2 kW208 V14.5 kW14.5 kW97.0%400–600 VFeb 1, 2018SB1
SE50KUS50 kW208 V16.6 kW16.6 kW97.0%400–600 VDec 13, 2021SB5
SE66.6KUS66.6 kW480 V33.3 kW33.3 kW98.5%790–950 VFeb 1, 2018SB2
SE80KUS80 kW480 V40.3 kW40.3 kW98.5%790–950 VJul 1, 2021SB1
SE100KUS100 kW480 V33.3 kW33.3 kW98.5%790–950 VFeb 1, 2018SB2
SE110KUS110 kW480 V110 kW110 kW98.5%795–950 VNov 21, 2023SB—
SE120KUS120 kW480 V40.3 kW40.3 kW98.5%790–950 VJul 1, 2021SB2
SE250KUS250 kW600 V249.9 kW249.9 kW99.0%1,090–1,320 VApr 1, 2025SB—
SE285KUS285 kW600 V284.2 kW284.2 kW99.0%1,090–1,320 VApr 1, 2025SB—
SE330KUS330 kW690 V329.7 kW329.7 kW99.0%1,200–1,400 VJul 11, 2025SB—

DC input (PV side)

CEC Grid Support Inverter List (Oct 7, 2026) · NLR SAM inverter library

AC output (grid side)

CEC Grid Support Inverter List (Oct 7, 2026)

Efficiency

CEC Grid Support Inverter List (Oct 7, 2026) · NLR SAM inverter library
CEC weighted efficiency is measured by an accredited lab at six power levels and three DC voltages — the number to compare between inverters.

Grid & smart-inverter certification

CEC Grid Support Inverter List (Oct 7, 2026) · SolarEdge datasheet
UL 1741 SB is required for new interconnections in California (Rule 21) since 2026.

Safety & protection

SolarEdge datasheet

Monitoring & communication

SolarEdge datasheet · CEC Grid Support Inverter List (Oct 7, 2026)

Size, weight & environment

SolarEdge datasheet

Panel compatibility & string sizing

NLR SAM inverter library · NLR PVWatts v8 · CEC PV Module List · Cali-Graf calculation
SE50KUS: max DC 600 V · MPPT 400–600 V (CEC test window)

Most-permitted panels in Southern California

PanelPowerVoc coldVmp hotPanels per stringInstalled together
Qcells Q.PEAK DUO BLK ML-G10.C+ 410410 W48.1 V30.6 Vno fit—
Qcells Q.PEAK DUO BLK ML-G10+ 410410 W48.1 V30.6 Vno fit—
LONGi LR5-54HABB-400M400 W39.3 V25.3 Vno fit—
JA Solar JAM54S31-405/MR405 W39.4 V25.5 Vno fit—
Hyundai Solutions HiN-T440NF(BK)440 W40.9 V27 Vno fit—
Silfab Solar SIL-440QD440 W41.1 V28 Vno fit—
Qcells Q.TRON BLK M-G2+ 430430 W41.3 V28 Vno fit—
Qcells Q.TRON BLK M-G2.H+ 430430 W41.3 V28 Vno fit—
REC Group REC460AA Pure-RX460 W68.8 V47.1 Vno fit—
Elin (Sirius PV) ELNSM54M-HC-410410 W39.3 V25.3 Vno fit—
Qcells Q.TRON BLK M-G2.C+ 430430 W41.3 V28 Vno fit—
Tesla TSP-420420 W43.4 V27.7 Vno fit—
Usually installed with power optimizers: string length follows the optimizer rules, not panel voltage — use the manufacturer’s designer.
Voltage check only, from CEC panel data and NLR weather for the city. Final design must follow the inverter manual and NEC 690.7.

What it's installed with

building permits

Panels

Qcells Q.PEAK DUO
3
JinkoSolar JKMxxxM-72HL-TV
2

Optimizers

SolarEdge (model not specified)
4
SolarEdge Power Optimizer
2

Gateways & interfaces

IronRidge (model not specified)
3
Unirac (model not specified)
2
Permits naming both; 13 of 14 permits list other equipment.

Installed in Southern California

building permits
14
Permits name it
Feb 2021 – Jul 2026
4
Jurisdictions so far
LA County (unincorp.) (9), Los Angeles (3), Chula Vista (1), Los Angel
85.3 kW
Typical system
median of 8 permits

Permits over time

1Q1 ’2110Q3 ’2101Q1 ’2200Q3 ’2210Q1 ’2321Q3 ’2310Q1 ’2402Q3 ’2401Q1 ’2510Q3 ’2510Q1 ’2601Q3 ’26permits per quarter

Model named in permit

SE50KUS
5
SE120KUS
2
SE40KUS
2
SE100KUS
2
SE66.6KUS
2
SE17.3KUS
2
Only installer and ZIP level is shown — no homeowner names, street addresses or permit numbers. Permits from LA County (unincorp.), Los Angeles come without a contractor license, so they count toward totals but not toward installers. Counts grow as more permit portals are loaded.

Who installs SExKUS in SoCal

building permits · CSLB License Master

Compare with similar 50 kW inverters

CEC Grid Support Inverter List (Oct 7, 2026) · building permits
InverterPowerCEC weighted eff.DC test windowUL 1741 SBLatest CECSoCal permits
SolarEdge SExKUS9 kW–330 kW97.0%400–600 VYes202519
SMA STP xx-US-8027.5 kW–70 kW97.5%300–850 VYes2026—
Yaskawa Solectria Solar PVI-xxTL-20825 kW–50 kW96.5%200–850 VYes2025—
Solis (Ginlong Technologies) S5-GC60K-LV-US60 kW–60 kW98.0%400–650 VYes2025—
CPS (Chint Power Systems) SCAxxK-T-US-20850 kW–50 kW96.5%200–700 VYes2025—
Same type and grid voltage, power range covering this model; same fields from the same sources.

About SolarEdge

CEC Grid Support Inverter List (Oct 7, 2026)

Questions & answers

How efficient is the SolarEdge SExKUS?

The California Energy Commission lists a weighted efficiency of 96.5–99.0% for SolarEdge SExKUS models, measured at six power levels and three DC voltages.

What sizes does the SolarEdge SExKUS come in?

The CEC list includes 19 models from 9 kW to 330 kW AC: SE9KUS, SE10KUS, SE10KUS, SE14.4KUS, SE17.3KUS, SE20KUS, SE30KUS, SE33.3KUS….

Is the SolarEdge SExKUS certified to UL 1741 SB?

Yes — the CEC Grid Support Inverter List shows UL 1741 SB for 16 of 19 models.

What is the SE50KUS’s DC input voltage range?

CEC tested it at 400–600 V DC.

Who installs it in Southern California?

Building permits name this series 14 times (Feb 2021 – Jul 2026). The most active licensed installers are Grid Alternatives.

Sources

  1. California Energy Commission — Grid Support Inverter List (solar and battery inverters), data as of Oct 7, 2026. Manufacturer-reported, confirmed by CEC against certificates and test reports.
  2. SolarEdge — manufacturer datasheet “INVERTERS Three Phase Inverters for the 120/208V Grid”.
  3. NLR (formerly NREL) — System Advisor Model CEC inverter library (version 2026.7.3).
  4. NLR (formerly NREL) — PVWatts v8, NSRDB PSM v3 typical-year weather for Los Angeles, Palmdale, Riverside, Santa Clarita, Chula Vista, Huntington Beach.
  5. California Energy Commission — PV Module List (module electrical data for the compatibility check).
  6. Building permits — Los Angeles County Public Works (EPIC-LA, unincorporated areas) (Feb 2021 – May 2025); LADBS, City of Los Angeles (Jun 2023 – Oct 2025); City of Chula Vista (Jul 2026); LADBS, City of Los Angeles (Mar 2022). Equipment matched from permit descriptions by model number.
  7. Contractors State License Board — License Master (contractor names and license status), as of Oct 5, 2026.
  8. Cali-Graf calculations — formulas and inputs are shown next to each calculated value (efficiency from area, temperature-corrected voltages, string sizing, energy estimates).