String inverterSMA

SMA SHP FLEX-US-21

String inverter. 10 models, 55 kW–172 kW AC at 208 V / 320 V / 380 V / 385 V / 400 V / 420 V / 480 V / 600 V / 630 V / 660 V.

UL 1741 SBCEC listed · Nov 1, 2024
Model
  • Rated AC power112.7 kW
  • CEC weighted efficiency98.5%

Models & power ratings

CEC Grid Support Inverter List (Oct 7, 2026) · NLR SAM inverter library · 10 models
ModelNominal ACGrid voltageCEC continuousRated AC (SAM)CEC weighted eff.DC test windowCEC listedUL 1741 SB
SHP FLEX-US-2155 kW208 V55.1 kW55.1 kW97.0%372–1,195 VNov 21, 2024SB
SHP FLEX-US-2184.9 kW320 V84.9 kW84.9 kW98.0%495–1,195 VMar 11, 2025SB
SHP FLEX-US-21100.8 kW380 V100.8 kW100.8 kW98.0%582–1,195 VMar 11, 2025SB
SHP FLEX-US-21100.8 kW385 V100.8 kW100.8 kW98.0%582–1,195 VMar 11, 2025SB
SHP FLEX-US-21105 kW400 V105.6 kW105.6 kW98.0%590–1,200 VNov 1, 2024SB
SHP FLEX-US-21112.7 kW420 V112.7 kW112.7 kW98.5%630–1,195 VMar 11, 2025SB
SHP FLEX-US-21125 kW480 V125 kW125 kW98.5%705–1,200 VJan 2, 2025SB
SHP FLEX-US-21150 kW600 V150.1 kW150.1 kW99.0%880–1,200 VJan 2, 2025SB
SHP FLEX-US-21165 kW630 V165.7 kW165.7 kW99.0%925–1,200 VJan 2, 2025SB
SHP FLEX-US-21172 kW660 V172.8 kW172.8 kW99.0%968–1,200 VJan 2, 2025SB

DC input (PV side)

CEC Grid Support Inverter List (Oct 7, 2026) · NLR SAM inverter library

Efficiency

CEC Grid Support Inverter List (Oct 7, 2026) · NLR SAM inverter library
CEC weighted efficiency is measured by an accredited lab at six power levels and three DC voltages — the number to compare between inverters.

Grid & smart-inverter certification

CEC Grid Support Inverter List (Oct 7, 2026)
UL 1741 SB is required for new interconnections in California (Rule 21) since 2026.

Panel compatibility & string sizing

NLR SAM inverter library · NLR PVWatts v8 · CEC PV Module List · Cali-Graf calculation
SHP FLEX-US-21: max DC 1,195 V · MPPT 630–1,195 V (CEC test window)

Most-permitted panels in Southern California

PanelPowerVoc coldVmp hotPanels per stringInstalled together
Qcells Q.PEAK DUO BLK ML-G10.C+ 410410 W48.1 V30.6 V21–24—
Qcells Q.PEAK DUO BLK ML-G10+ 410410 W48.1 V30.6 V21–24—
LONGi LR5-54HABB-400M400 W39.3 V25.3 V25–30—
JA Solar JAM54S31-405/MR405 W39.4 V25.5 V25–30—
Hyundai Solutions HiN-T440NF(BK)440 W40.9 V27 V24–29—
Silfab Solar SIL-440QD440 W41.1 V28 V23–29—
Qcells Q.TRON BLK M-G2+ 430430 W41.3 V28 V23–28—
Qcells Q.TRON BLK M-G2.H+ 430430 W41.3 V28 V23–28—
REC Group REC460AA Pure-RX460 W68.8 V47.1 V14–17—
Elin (Sirius PV) ELNSM54M-HC-410410 W39.3 V25.3 V25–30—
Qcells Q.TRON BLK M-G2.C+ 430430 W41.3 V28 V23–28—
Tesla TSP-420420 W43.4 V27.7 V23–27—
Voltage check only, from CEC panel data and NLR weather for the city. Final design must follow the inverter manual and NEC 690.7.

About SMA

CEC Grid Support Inverter List (Oct 7, 2026)

Other series

STP xx-US-80STP xx-US-50SHP xxx-US-21

Questions & answers

How efficient is the SMA SHP FLEX-US-21?

The California Energy Commission lists a weighted efficiency of 97.0–99.0% for SMA SHP FLEX-US-21 models, measured at six power levels and three DC voltages.

What sizes does the SMA SHP FLEX-US-21 come in?

The CEC list includes 10 models from 55 kW to 172 kW AC: SHP FLEX-US-21, SHP FLEX-US-21, SHP FLEX-US-21, SHP FLEX-US-21, SHP FLEX-US-21, SHP FLEX-US-21, SHP FLEX-US-21, SHP FLEX-US-21….

Is the SMA SHP FLEX-US-21 certified to UL 1741 SB?

Yes — the CEC Grid Support Inverter List shows UL 1741 SB for all models.

What is the SHP FLEX-US-21’s DC input voltage range?

CEC tested it at 630–1,195 V DC.

Sources

  1. California Energy Commission — Grid Support Inverter List (solar and battery inverters), data as of Oct 7, 2026. Manufacturer-reported, confirmed by CEC against certificates and test reports.
  2. NLR (formerly NREL) — System Advisor Model CEC inverter library (version 2026.7.3).
  3. NLR (formerly NREL) — PVWatts v8, NSRDB PSM v3 typical-year weather for Los Angeles, Palmdale, Riverside, Santa Clarita, Chula Vista, Huntington Beach.
  4. California Energy Commission — PV Module List (module electrical data for the compatibility check).
  5. Cali-Graf calculations — formulas and inputs are shown next to each calculated value (efficiency from area, temperature-corrected voltages, string sizing, energy estimates).